Computation of Cable Ampacity by Finite Element Method Under Voluntary Conditions

Amin Mahmoudi, Solmaz Kahourzade, R. K. Lalwani

Research output: Contribution to journalArticle

4 Citations (Scopus)

Abstract

This paper presents a new approach for the determination of underground cable ampacity that considers natural convection of air inside a conduit and heterogeneous soil around the conduit, and compares calculated results with conduit-less considerations. It shows how ampacity of a buried cable is affected by thickness of the soil above it, and by the surrounding soil's heterogeneity and thermo-physical characteristic. Commercial ANSYS software for three-dimensional simulation of a 400kV polyethylene-paper cables with copper segments is used. The investigation yields numerical solutions for Fourier conducting heat transfer, continuity, energy, and momentum equations. Poor convection of air in conduit is shown to result in cable threshold temperature to be greater than that in conduit-less, other conditions being similar. Also results show that the longer the conduit, the lesser the acceptable ampacity. The proposed method gives criterion and flexibility to change strategy for situations which are not discussed in standard literature on cable routing.

Original languageEnglish
Pages (from-to)135-146
Number of pages12
JournalAustralian Journal of Basic and Applied Sciences
Volume5
Issue number5
Publication statusPublished - May 2011
Externally publishedYes

Keywords

  • Ampacity
  • ANSYS
  • Finite Element Method
  • Underground Cables

Fingerprint Dive into the research topics of 'Computation of Cable Ampacity by Finite Element Method Under Voluntary Conditions'. Together they form a unique fingerprint.

  • Cite this